- θ
- Pitch: the angle of the roof slope from flat, in degrees
- h
- Rise: the height from the top of the wall to the ridge
- r
- Run: from the outside of the wall to the centre line of the ridge (half the span)
- L
- Rafter length: wall to ridge along the slope, before any overhang (run × rafter factor)
- x
- Rise in 12: how far the roof rises for every 12 across (6/12 rises 6 inches per foot)
Roof pitch in degrees
| Pitch | Rise per metre of run (mm) | Rise in 12 (in per foot) | Slope (%) | Rafter factor |
|---|---|---|---|---|
| 2.5° | 44 | 0.5 | 4.4 | 1.001 |
| 5° | 87 | 1 | 8.7 | 1.004 |
| 7.5° | 132 | 1.6 | 13.2 | 1.009 |
| 10° | 176 | 2.1 | 17.6 | 1.015 |
| 12.5° | 222 | 2.7 | 22.2 | 1.024 |
| 15° | 268 | 3.2 | 26.8 | 1.035 |
| 17.5° | 315 | 3.8 | 31.5 | 1.049 |
| 20° | 364 | 4.4 | 36.4 | 1.064 |
| 22.5° | 414 | 5 | 41.4 | 1.082 |
| 25° | 466 | 5.6 | 46.6 | 1.103 |
| 27.5° | 521 | 6.2 | 52.1 | 1.127 |
| 30° | 577 | 6.9 | 57.7 | 1.155 |
| 32.5° | 637 | 7.6 | 63.7 | 1.186 |
| 35° | 700 | 8.4 | 70 | 1.221 |
| 37.5° | 767 | 9.2 | 76.7 | 1.260 |
| 40° | 839 | 10.1 | 83.9 | 1.305 |
| 42.5° | 916 | 11 | 91.6 | 1.356 |
| 45° | 1000 | 12 | 100 | 1.414 |
| 47.5° | 1091 | 13.1 | 109.1 | 1.480 |
| 50° | 1192 | 14.3 | 119.2 | 1.556 |
| 52.5° | 1303 | 15.6 | 130.3 | 1.643 |
| 55° | 1428 | 17.1 | 142.8 | 1.743 |
| 57.5° | 1570 | 18.8 | 157 | 1.861 |
| 60° | 1732 | 20.8 | 173.2 | 2.000 |
UK roof tiles and slates each have a minimum pitch: often 15° to 22.5° for interlocking tiles, 30° or more for plain tiles and many slates. Check the maker's figure, which can depend on the rafter length and how exposed the site is.
Roof pitch as a rise in 12
| Pitch | Degrees (°) | Slope (%) | Rise per metre of run (mm) | Rafter factor |
|---|---|---|---|---|
| 1/12 | 4.8 | 8.3 | 83 | 1.003 |
| 2/12 | 9.5 | 16.7 | 167 | 1.014 |
| 3/12 | 14 | 25 | 250 | 1.031 |
| 4/12 | 18.4 | 33.3 | 333 | 1.054 |
| 5/12 | 22.6 | 41.7 | 417 | 1.083 |
| 6/12 | 26.6 | 50 | 500 | 1.118 |
| 7/12 | 30.3 | 58.3 | 583 | 1.158 |
| 8/12 | 33.7 | 66.7 | 667 | 1.202 |
| 9/12 | 36.9 | 75 | 750 | 1.250 |
| 10/12 | 39.8 | 83.3 | 833 | 1.302 |
| 11/12 | 42.5 | 91.7 | 917 | 1.357 |
| 12/12 | 45 | 100 | 1000 | 1.414 |
| 13/12 | 47.3 | 108.3 | 1083 | 1.474 |
| 14/12 | 49.4 | 116.7 | 1167 | 1.537 |
| 15/12 | 51.3 | 125 | 1250 | 1.601 |
| 16/12 | 53.1 | 133.3 | 1333 | 1.667 |
| 17/12 | 54.8 | 141.7 | 1417 | 1.734 |
| 18/12 | 56.3 | 150 | 1500 | 1.803 |
| 19/12 | 57.7 | 158.3 | 1583 | 1.873 |
| 20/12 | 59 | 166.7 | 1667 | 1.944 |
| 21/12 | 60.3 | 175 | 1750 | 2.016 |
| 22/12 | 61.4 | 183.3 | 1833 | 2.088 |
| 23/12 | 62.4 | 191.7 | 1917 | 2.162 |
| 24/12 | 63.4 | 200 | 2000 | 2.236 |
US roofers give pitch as the rise in inches for every 12 inches (1 foot) across: a 6/12 roof rises 6 inches per foot of run. 12/12 is 45°.
About this chart
Roof pitches three ways: in degrees (used in the UK and Europe), as a rise in 12 (used in the US, such as 6/12) and as a percentage slope. Choose degrees or rise in 12 above the chart.
Rise per metre of run tells you how high the roof climbs for each metre across, so a 30° roof with a 4 m run rises 4 × 577 = 2,309 mm. The rafter factor turns a run into a rafter length (or a flat plan area into the area of roof slope): 4 m × 1.155 = 4.62 m of rafter, before any overhang.
For your own rise and run, or the roof height for a chosen pitch, use the roof pitch calculator.
How it's worked out (rise ÷ run is the same in any unit):
- Degrees = tan⁻¹(rise ÷ run); from degrees, rise ÷ run = tan(pitch)
- Rise in 12 = rise ÷ run × 12, rounded to 0.1
- Slope % = rise ÷ run × 100
- Rise per metre of run = rise ÷ run × 1,000 mm. The rise in 12 is also the rise in inches per foot of run
- Rafter factor = √(rise² + run²) ÷ run, which is 1 ÷ cos(pitch). Multiply the run by it for the rafter length to the ridge centre line, or a flat plan area by it for the area of roof slope (for tiles or felt). Add any overhang and allow for the ridge board on top.