Cable Voltage Drop Calculator

Check the voltage drop on a copper cable run against the UK wiring regulations' 3% and 5% limits, with the longest run and smallest cable that pass.

New: please check your results.

For guidance only. This is not a substitute for a qualified engineer, and important designs should be checked by one.

Voltage drop
7.2 V
As a share of the supply
3.13 %
Result
Within the 5% limit
Longest run within the limit
31.9 m
Smallest cable within the limit
2.5 mm²
mV/A/m used
18
Convert 104.8 ft
A

m

V

What it does

Check how much voltage is lost along a copper cable before it reaches the load, and whether it's within the limits recommended by BS 7671, the UK wiring regulations: 3% for lighting and 5% for other circuits. Enter the current, the length of the run and the cable size. It also shows the longest run that stays within the limit and the smallest standard cable that would.

How to use it

Current

The design current of the circuit: what the load draws, or the rating of the protective device (MCB) to be safe. For watts, use the watts to amps calculator.

Cable length (one way)

From the consumer unit or distribution board to the load, along the route the cable takes. Don't double it: the calculation allows for the return conductor.

Supply

Homes are single-phase. Three-phase is for larger motors, workshops and commercial supplies.

Supply voltage

230 V in the UK.

Line voltage

400 V between phases in the UK.

Cable size

The cross-section of each conductor, printed on the sheath. Ring and radial socket circuits are usually 2.5 mm², lighting 1.0 or 1.5 mm², cookers and showers 6 or 10 mm².

Insulation

PVC for twin and earth and most flex; XLPE for most armoured (SWA) cable. Hotter-running cables have higher resistance, so a slightly bigger drop. Check the cable's datasheet if unsure.

Voltage drop per amp per metre

From the cable maker's datasheet or the BS 7671 Appendix 4 tables, for aluminium, flexible cords or sizes over 35 mm².

Circuit for

BS 7671 recommends these limits for installations fed from the public supply. Private supplies allow 6% and 8%.

Common uses

  • Checking a long run to a garage, garden office or outbuilding.
  • Sizing the cable for an electric shower, cooker or car charger.
  • Checking a submain or armoured cable run.
  • Working out the current from an appliance's watts. Try the Watts to Amps Calculator
  • Working out volts, amps or ohms from the other two. Try the Ohm's Law Calculator

The formula

Voltage drop (V) = mV/A/m × current (A) × length (m) ÷ 1,000Share of supply = voltage drop ÷ supply voltage × 100Longest run = (limit × supply voltage) × 1,000 ÷ (mV/A/m × current)

Where:

mV/A/m
millivolts lost per amp per metre of run, for that cable size, from BS 7671 Appendix 4
length
one way: the tabulated value already includes the return conductor

Uses tabulated values for copper conductors at full operating temperature, which is cautious: a lightly loaded cable runs cooler and drops a little less. Reactance is ignored, which is accurate up to 35 mm².

Worked example

A 20 m run of 2.5 mm² PVC cable carrying 20 A:

  • From the BS 7671 tables, 2.5 mm² cable drops 18 mV/A/m on single-phase
  • Voltage drop: 18 × 20 × 20 ÷ 1,000 = 7.2 V
  • As a share: 7.2 V ÷ 230 V = 3.13 %, within the 5% limit (11.5 V)

Questions people ask

What voltage drop is allowed in the UK?

BS 7671 Appendix 4 recommends no more than 3% for lighting and 5% for other uses, from the origin of the installation, when it's fed from the public supply. On 230 V that's 6.9 V and 11.5 V.

Is voltage drop the only thing that sets cable size?

No. The cable must also carry the current without overheating (its current rating depends on how it's installed, insulation around it and grouping with other cables), and the circuit must disconnect fast enough in a fault. Use this for the voltage drop check; a qualified electrician should design and certify new circuits.

Should I measure the length both ways?

No. Enter the one-way route length. The mV/A/m figures already include both the line and neutral (or all three phases).