Cable Voltage Drop Table

Voltage drop in mV/A/m for copper cable from 1 to 35 mm², PVC and XLPE, single and three-phase, and the longest run within 3% and 5%.

Download the chart

The diagram and chart are sized to fit one page. For a PDF, choose Save as PDF in the print window.

I VV − ΔV Consumer unitLoad L
L
Length: the one-way route from the consumer unit to the load. Don't double it; the tables allow for the return
I
Current: the circuit's design current, or the breaker rating to be safe
V
Supply voltage: 230 V single-phase, 400 V between phases on three-phase
ΔV
Voltage drop: mV/A/m × I × L ÷ 1,000. At most 3% of V for lighting, 5% for other circuits
Every metre of cable has a little resistance, so the voltage at the load is lower than at the consumer unit. Longer runs and higher currents need thicker cable.

Voltage drop per amp per metre (mV/A/m)

CablePVC single-phasePVC three-phaseXLPE single-phaseXLPE three-phase
1.0 mm²44384640
1.5 mm²29253127
2.5 mm²18151916
4 mm²119.51210
6 mm²7.36.47.96.8
10 mm²4.43.84.74
16 mm²2.82.42.92.5
25 mm²1.751.51.851.6
35 mm²1.251.11.351.15

Copper conductors at full operating temperature: 70 °C for PVC (twin and earth, most flex), 90 °C for XLPE (most armoured SWA). A lightly loaded cable runs cooler and drops a little less, so these are on the safe side.

Longest run within 5%: single-phase PVC (230 V)

Cable6 A (m)10 A (m)16 A (m)20 A (m)25 A (m)32 A (m)40 A (m)45 A (m)50 A (m)63 A (m)
1.0 mm²43.626.116.313.110.58.26.55.85.24.1
1.5 mm²66.139.724.819.815.912.49.98.87.96.3
2.5 mm²10663.939.931.925.6201614.212.810.1
4 mm²17410565.352.341.832.726.123.220.916.6
6 mm²26315898.578.86349.239.43531.525
10 mm²43626116313110581.765.358.152.341.5
16 mm²68541125720516412810391.382.165.2
25 mm²1095657411329263205164146131104
35 mm²1533920575460368288230204184146

Sockets, cookers, showers and other non-lighting circuits: 5% of 230 V is 11.5 V. Voltage drop only: the cable must also be rated for the current where it's installed (clipped, in a wall, in insulation or grouped with others), and the circuit must disconnect fast enough in a fault. A qualified electrician should design and certify new circuits.

Longest run within 3%: lighting, single-phase PVC (230 V)

Cable3 A (m)6 A (m)10 A (m)16 A (m)20 A (m)
1.0 mm²52.326.115.79.87.8
1.5 mm²79.339.723.814.911.9
2.5 mm²12863.938.32419.2
4 mm²20910562.739.231.4
6 mm²31515894.559.147.3
10 mm²5232611579878.4
16 mm²821411246154123
25 mm²1314657394246197
35 mm²1840920552345276

Lighting circuits: 3% of 230 V is 6.9 V. Voltage drop only: the cable must also be rated for the current where it's installed (clipped, in a wall, in insulation or grouped with others), and the circuit must disconnect fast enough in a fault. A qualified electrician should design and certify new circuits.

Longest run within 5%: single-phase XLPE (230 V)

Cable6 A (m)10 A (m)16 A (m)20 A (m)25 A (m)32 A (m)40 A (m)45 A (m)50 A (m)63 A (m)
1.0 mm²41.72515.612.5107.86.35.654
1.5 mm²61.837.123.218.514.811.69.38.27.45.9
2.5 mm²10160.537.830.324.218.915.113.512.19.6
4 mm²16095.859.947.938.329.92421.319.215.2
6 mm²2431469172.858.245.536.432.329.123.1
10 mm²40824515312297.976.561.254.448.938.8
16 mm²66139724819815912499.188.179.362.9
25 mm²103662238931124919415513812498.7
35 mm²1420852532426341266213189170135

Armoured (SWA) cable to a garage, garden office or car charger is usually XLPE. Voltage drop only: the cable must also be rated for the current where it's installed (clipped, in a wall, in insulation or grouped with others), and the circuit must disconnect fast enough in a fault. A qualified electrician should design and certify new circuits.

Longest run within 5%: three-phase PVC (400 V)

Cable6 A (m)10 A (m)16 A (m)20 A (m)25 A (m)32 A (m)40 A (m)45 A (m)50 A (m)63 A (m)
1.0 mm²87.752.632.926.321.116.413.211.710.58.4
1.5 mm²13380504032252017.81612.7
2.5 mm²22213383.366.753.341.733.329.626.721.2
4 mm²35121113210584.265.852.646.842.133.4
6 mm²52131319515612597.778.169.462.549.6
10 mm²87752632926321116413211710583.5
16 mm²1389833521417333260208185167132
25 mm²22221333833667533417333296267212
35 mm²303018181136909727568455404364289

5% of 400 V is 20 V. Voltage drop only: the cable must also be rated for the current where it's installed (clipped, in a wall, in insulation or grouped with others), and the circuit must disconnect fast enough in a fault. A qualified electrician should design and certify new circuits.

Longest run within 5%: three-phase XLPE (400 V)

Cable6 A (m)10 A (m)16 A (m)20 A (m)25 A (m)32 A (m)40 A (m)45 A (m)50 A (m)63 A (m)
1.0 mm²83.35031.3252015.612.511.1107.9
1.5 mm²12374.146.33729.623.118.516.514.811.8
2.5 mm²20812578.162.55039.131.327.82519.8
4 mm²3332001251008062.55044.44031.7
6 mm²49029418414711891.973.565.458.846.7
10 mm²83350031325020015612511110079.4
16 mm²1333800500400320250200178160127
25 mm²20831250781625500391313278250198
35 mm²289917391087870696543435386348276

5% of 400 V is 20 V. Voltage drop only: the cable must also be rated for the current where it's installed (clipped, in a wall, in insulation or grouped with others), and the circuit must disconnect fast enough in a fault. A qualified electrician should design and certify new circuits.

About this chart

How much voltage copper cable loses, and the longest run that stays within the UK wiring regulations' limits: 3% for lighting and 5% for everything else (BS 7671 Appendix 4, for an installation fed from the public supply). Choose a table above the chart.

mV/A/m is millivolts lost for every amp and every metre of run. Multiply by the current and the length to get the drop: 2.5 mm² PVC on single-phase is 18 mV/A/m, so 20 A over 20 m drops 18 × 20 × 20 ÷ 1,000 = 7.2 V.

For your own run, or to check a cable that's already in, use the cable voltage drop calculator.

How it's worked out:

  • Voltage drop (V) = mV/A/m × current (A) × length (m) ÷ 1,000
  • Longest run (m) = limit (V) × 1,000 ÷ (mV/A/m × current), with the limit 3% or 5% of 230 V (6.9 V or 11.5 V), or of 400 V for three-phase (20 V at 5%)

The mV/A/m values are BS 7671 Appendix 4's tables for copper (4D1B, 4D2B and 4D5 for 70 °C PVC; 4E1B and 4E2B for 90 °C XLPE), checked by working them out from the conductor resistances in BS EN 60228. Reactance is ignored, which is accurate up to 35 mm². The limits apply from the origin of the installation, so any drop in a submain counts too. Private supplies allow 6% and 8%.